poles description |
3P |
utilisation category |
Category A conforming to IEC 60947-2 |
motor power kW |
55…75 kW at 400/415 V AC 50/60 Hz
75…90 kW at 500 V AC 50/60 Hz
90…110 kW at 660/690 V AC 50/60 Hz |
breaking capacity |
36 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity |
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
control type |
Direct rotary handle |
[In] rated current |
150 A at 65 °C |
magnetic tripping current |
2250 A |
[Ue] rated operational voltage |
690 V AC 50/60 Hz |
[Ui] rated insulation voltage |
800 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ith] conventional free air thermal current |
150 A conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage |
8 kV |
power dissipation per pole |
9.2 W |
mechanical durability |
40000 cycles |
electrical durability |
20000 cycles for AC-3 at 400/415 V In |
maximum operating rate |
25 cyc/h |
rated duty |
Continuous |
connection pitch |
35 mm without spreaders |
connections – terminals |
Bars
Lugs |
tightening torque |
15 N.m M8 screw type |
mechanical robustness |
Vibrations: +/- 1 mm 2…13.2 Hz conforming to IEC 60068-2-6
Vibrations: 0.7 gn 13.2…100 Hz conforming to IEC 60068-2-6 |
phase failure sensitivity |
Yes conforming to IEC 60947-4-1 |
Height |
161 mm |
width |
105 mm |
Depth |
155 mm |
Net weight |
2.4 kg |
colour |
Anthracite (RAL 7016) |
suitability for isolation |
Yes conforming to EN/IEC 60947-2 |